VJS7 Potentiometer Converter

Brand: Yokogawa Electric Corporation

The VJS7 is a compact, plug-in potentiometer converter that is used in combination with an instrument to transmit information for displacement of valve, etc. by resistance change of potentiometer. 

It converts the resistance changes into isolated DC current or DC voltage signals.
Features
  • Output-2 can be selected from DC voltage signal, DC current signal, communication output (RS-485) or alarm output (2 relay contacts)
  • Various parameters such as input range can be set and modified using a PC (VJ77) or handy terminal (JHT200 or the like)

Specifications

Accuracy

  • ± 0.1 % of Span

Alarm

  • 0 to 100 % of Input Range - Alarm Setting Range
  • High/Low Limit - Alarm Operating Direction

Approvals & Certifications

  • CAN/CSA C22.2 No. 61010-1
  • CE EN 61326-1
  • EMC
  • KC
  • UL 61010-1

Burn-Out

  • Downscale
  • Off
  • Upscale
  • Within 60 seconds - Burn-Out Time

Communication

  • 2-Wire Half-Duplex (Start-Stop Synchronization, Non-procedural)
  • Baud Rate: 1,200, 2,400, 4,800, 9,600 bit/sec
  • Data Length: 7-bits, 8-bits
  • EIA RS-485
  • LADDER Communication
  • Modbus ASCII/RTU
  • PC-Link Communication Protocol
  • PC-Link with Sum
  • Stop Bit: 1-bit, 2-bits

Display

  • Front LED Lights at Alarm, 2 LEDs - Alarm Operation Display

Dissipation

  • 2.5 W at 24 Vdc - Power Dissipation
  • 2.6 W at 110 Vdc - Power Dissipation
  • 5 VA at 100 Vac - Power Dissipation
  • 6.7 VA at 200 Vac - Power Dissipation

Distance

  • 3,937 feet (1,200 metres) - Max.

Electrical Connectors

  • M3 Screw Terminal

Electrical Contacts

  • Normally Open Contact Output (Contact ON at Excitation) 2-Points, COM Common - Output Signal

Electrical Rating

  • 1 A at 30 Vdc - Contact Capacity

Enclosure, Body Material

  • Modified Polyphenylene Oxide

Frequency

  • 47 to 63 Hz

Humidity

  • 5 to 90 % RH, Non-Condensing

Hysteresis

  • 0 to 100 % of Input Range - Hysteresis Setting Range
  • 3 % (Alarm-1/2)

Input

  • 3-wire Potentiometer (Full Resistance: 100 to 10,00 kΩ)
  • 50 % or Less of Full Resistance or 1 kΩ per Leadwire, Equal or Less than whichever is Small - Permissible Input Conductor Resistance

Insulation Resistance

  • 100 MΩ at 500 Vdc between Input, Output-1, Output-2, Power Supply & Ground Mutually

Measurement Accuracy

  • Within ± 20 % of the Range During Testing

Measuring Span

  • 50 to 10,000 ohms

Measuring Voltage

  • 0.5 Vdc Approximately

Mounting

  • Base Mounting (Only when Output 2 is Analog Output) - VJ Mounting
  • Compact Plug-In Typical - Construction
  • DIN Rail Mounting
  • Wall Mounted

Output

  • 0-100 mVdc
  • 0-20 mA DC
  • -10 to 10 Vdc
  • 1-5 Vdc
  • 4-20 mA DC

Output Format

  • Relay Contact - Signal Typical for Alarm Output

Power Supply

  • 100-240 Vac/dc (-15 %, 10 %) 50/60 Hz - Power Supply Input & Rated Voltage
  • 15-30 Vdc (± 20 %) - Power Supply Input & Rated Voltage

Power Supply Effect

  • ± 0.1 % or Less of Span for Fluctuation of 85-264 Vac/dc (47-63 Hz) & 12-36 Vdc - Effect of Power Supply Voltage Fluctuation

Relay Output

  • 2 Relay Contacts - Alarm Output

Resistance

  • 0 to 1,000 ohms - Factory Setting of Input Range
  • 1 ohm or Less - Output Resistance
  • 100 ohms or Less - Output Resistance
  • 100 to 10,000 ohms - Full Resistance of Measuring Range
  • 350 to 250,000 ohms - Permissible Load Resistance
  • 500 kΩ or more - Output Resistance

Resolution

  • 0.1 %, 4 Significant Digits - Setting Resolution
  • 1 second - Setting Resolution

Response Time

  • 150 ms, 63 % Response (10 to 90 %)
  • 350 ms (Input Change 10 to 90 %, Alarm Setting Point 50 %) - Alarm Output

Span & Zero Adjustments

  • ± 10 % of Span - Output Span Adjustment
  • ± 5 % - Output Zero Adjustment
  • ± 5 % of Span (Output-1 Signal: -10-10 Vdc) - Output Span Adjustment

Supply Voltage

  • 1,000 Vac/minute between Output 1, Output-2 & Input, Output-2 when Alarm Output - Withstand Voltage
  • 12-36 Vdc - Power Supply Voltage Fluctuation
  • 2,000 Vac/minute between Input, Output-1, Output-2, Power Supply & Ground Mutually - Withstand Voltage
  • 85-264 Vac/dc (47 to 63 Hz) - Power Supply Voltage Fluctuation

Temperature Effect

  • ± 0.2 % or Less of Span for Change of 10° C (18° F) - Effect of Ambient Temperature

Temperature Range

  • 0° to 50° C (32° to 122° F)

Version / Leadwires

  • 3-Wire Typical (Potentiometer)

Zero Offset

  • 50 % of Full Resistance or Less - Zero Elevation

show more