Alarm
- 0 to 100 % of Input Range - Alarm Setting Range
- High/Low Limit - Alarm Operating Direction
Approvals & Certifications
- CAN/CSA C22.2 No. 61010-1
- CE EN 61326-1
- EMC
- KC
- UL 61010-1
Burn-Out
- Downscale
- Off
- Upscale
- Within 60 seconds - Burn-Out Time
Communication
- 2-Wire Half-Duplex (Start-Stop Synchronization, Non-procedural)
- Baud Rate: 1,200, 2,400, 4,800, 9,600 bit/sec
- Data Length: 7-bits, 8-bits
- EIA RS-485
- LADDER Communication
- Modbus ASCII/RTU
- PC-Link Communication Protocol
- PC-Link with Sum
- Stop Bit: 1-bit, 2-bits
Display
- Front LED Lights at Alarm, 2 LEDs - Alarm Operation Display
Dissipation
- 2.5 W at 24 Vdc - Power Dissipation
- 2.6 W at 110 Vdc - Power Dissipation
- 5 VA at 100 Vac - Power Dissipation
- 6.7 VA at 200 Vac - Power Dissipation
Distance
- 3,937 feet (1,200 metres) - Max.
Electrical Contacts
- Normally Open Contact Output (Contact ON at Excitation) 2-Points, COM Common - Output Signal
Electrical Rating
- 1 A at 30 Vdc - Contact Capacity
Enclosure, Body Material
- Modified Polyphenylene Oxide
Humidity
- 5 to 90 % RH, Non-Condensing
Hysteresis
- 0 to 100 % of Input Range - Hysteresis Setting Range
- 3 % (Alarm-1/2)
Input
- 3-wire Potentiometer (Full Resistance: 100 to 10,00 kΩ)
- 50 % or Less of Full Resistance or 1 kΩ per Leadwire, Equal or Less than whichever is Small - Permissible Input Conductor Resistance
Insulation Resistance
- 100 MΩ at 500 Vdc between Input, Output-1, Output-2, Power Supply & Ground Mutually
Measurement Accuracy
- Within ± 20 % of the Range During Testing
Mounting
- Base Mounting (Only when Output 2 is Analog Output) - VJ Mounting
- Compact Plug-In Typical - Construction
- DIN Rail Mounting
- Wall Mounted
Output
- 0-100 mVdc
- 0-20 mA DC
- -10 to 10 Vdc
- 1-5 Vdc
- 4-20 mA DC
Output Format
- Relay Contact - Signal Typical for Alarm Output
Power Supply
- 100-240 Vac/dc (-15 %, 10 %) 50/60 Hz - Power Supply Input & Rated Voltage
- 15-30 Vdc (± 20 %) - Power Supply Input & Rated Voltage
Power Supply Effect
- ± 0.1 % or Less of Span for Fluctuation of 85-264 Vac/dc (47-63 Hz) & 12-36 Vdc - Effect of Power Supply Voltage Fluctuation
Relay Output
- 2 Relay Contacts - Alarm Output
Resistance
- 0 to 1,000 ohms - Factory Setting of Input Range
- 1 ohm or Less - Output Resistance
- 100 ohms or Less - Output Resistance
- 100 to 10,000 ohms - Full Resistance of Measuring Range
- 350 to 250,000 ohms - Permissible Load Resistance
- 500 kΩ or more - Output Resistance
Resolution
- 0.1 %, 4 Significant Digits - Setting Resolution
- 1 second - Setting Resolution
Response Time
- 150 ms, 63 % Response (10 to 90 %)
- 350 ms (Input Change 10 to 90 %, Alarm Setting Point 50 %) - Alarm Output
Span & Zero Adjustments
- ± 10 % of Span - Output Span Adjustment
- ± 5 % - Output Zero Adjustment
- ± 5 % of Span (Output-1 Signal: -10-10 Vdc) - Output Span Adjustment
Supply Voltage
- 1,000 Vac/minute between Output 1, Output-2 & Input, Output-2 when Alarm Output - Withstand Voltage
- 12-36 Vdc - Power Supply Voltage Fluctuation
- 2,000 Vac/minute between Input, Output-1, Output-2, Power Supply & Ground Mutually - Withstand Voltage
- 85-264 Vac/dc (47 to 63 Hz) - Power Supply Voltage Fluctuation
Temperature Effect
- ± 0.2 % or Less of Span for Change of 10° C (18° F) - Effect of Ambient Temperature
Temperature Range
- 0° to 50° C (32° to 122° F)
Version / Leadwires
- 3-Wire Typical (Potentiometer)
Zero Offset
- 50 % of Full Resistance or Less - Zero Elevation