HIMHART Smart HART Loop Interface & Monitor

Brand: Yokogawa Electric Corporation

The HIMHART Loop Interface and Monitor unlocks the full potential of new and in-place smart HART multivariable transmitters and valves.

Converts HART to 4-20 mA Signals: The HIM allows up to three additional Analog process variable measurements from a smart device with no additional process penetrations or wiring.

Take Full Advantage of “Legacy” Instruments: The HIM lets you leave trusted (and paid for) smart HART transmitters and valves in place, yet still take advantage of all the information they have to offer.
Features
  • "Break Out" up to three analog signals proportional to a HART primary, second, third or fourth variables of multivariable transmitters
  • High/Low process and loop diagnostic alarms
  • Normal or Burst HART Modes
  • Sets up as a Primary or Secondary Master, or in "Listen" Mode
  • Large, 5-digit display
  • Isolated output channels

Specifications

Accuracy

  • ± 0.015 % of, Max.

Alarm

  • Process High/Low Alarms

Approvals & Certifications

  • CE
  • CSA
  • EMC Directive 89/336/EEC, EN 61326

Communication

  • Baud Rate: 300 to 19,200 bit/sec
  • Data Length: 8-bits - Character Format
  • HART
  • RS-485 Modbus RTU Communication Protocol
  • Start Bit: 1-bit - Character Format
  • Stop Bit: 1-bit - Character Format

Consumption

  • 2 to 3.5 W, Nominal
  • 4.5 W at 24 Vdc, Max.

Delay Time

  • 0 to 120 seconds Programmable - Alarm Trip Delay

Diagnostics

  • Process & Status High/Low Alarm

Display

  • 2-Digit HART Address Indicator
  • -99999 to 99999
  • Bottom Row, 0.225" (6 mm) High Digits on a Reflective Background
  • Large, 5-Digit Display
  • Top Row, 0.4" (10 mm) High Black Digits on a Reflective Background
  • Two-Line LCD Display

Electrical Connectors

  • Terminal Blocks Can Accommodate 14 to 22 AWG Solid Wiring (Torque to 4 in/lb, max.

Electrical Contacts

  • Normally Closed
  • Normally Open

Electrical Rating

  • 5 A at 250 Vac, 50/60 Hz

Environmental Protection

  • Hazardous Area Class I, Div. 2, Groups A, B, C, D
  • Non-Incendive Apparatus Class I, Div. 2, Groups A, B, C, D

Humidity

  • 0 to 95 % Non-Condensing - Relative Humidity

Indication

  • Green Status LED of Alarm Off - TRIP 1 & 2 LED
  • LED - Dual Color Red/Green Indicates Input & Ready Status
  • Red Status LED of Alarm on - TRIP 1 & 2 LED

Input

  • ± 5 Vdc Protection - Input Over-Range

Input Impedance

  • 150 ohms - Transmit Mode
  • Less than 5 kΩ - Receive Mode

Isolation

  • 1,000 Vrms between Case, Input, Outputs & Power Terminals
  • 1,500 Vac Dielectric Strength Test for One Minute with No Breakdown
  • 500 Vrms - Channel to Channel Isolation

Line Voltage Effect

  • ± 0.005 % of Output Span for a 1 % Change in Line Voltage

Load

  • 1,100 ohms - for Communications
  • 250 ohms - for Communications

Load Effect

  • ± 0.01 % of Span from 0 To, Max.

Mounting

  • Surface
  • Top Hat DIN Rail Mounting

Operating Temperature

  • -25° to 70° C (-13° to 158° F) - Relay Range for Ambient Conditions
  • -25° to 85° C (-13° to 185° F) - Display Range for Ambient Conditions
  • -40° to 85° C (-40° to 185° F) - for Ambient Conditions

Output

  • 0-20 mA: Fail Low to 0 mA or Fail High to 23.6 mA - Output Limits on Input Failure
  • 4-20 mA: Fail Low to 3.6 mA or Fail High to 23.6 mA - Output Limits on Input Failure
  • Ripple: < 10 mV Peak-to-Peak when Measured Across A 250 ohms Resistor

Output Noise

  • 100 dB at 50/60 Hz - Common Mode for Noise Rejection

Power

  • 24 Vdc ± 10 %

Response Time

  • < 120 mss, 10 to 90 % - Output Response Time
  • 150 ms + Digital Response Time - Alarm Response Time
  • 333 ms, max.
  • 500 ms, max.

RFI/EMI Effect

  • 20 V/m at 20 to 1,000 MHz, 1 kHz AM, when Tested According to IEC 1000-4-3-1995 - RFI/EMI Immunity
  • 30 V/m at 20 to 1,000 MHz, 1 kHz, when Tested According to IEC 1000-4-3-1995 - RFI/EMI Immunity

Span - Maximum

  • 125 % of Span Typical - Output Limiting
  • 130 % of Span - Output Limiting

Span - Minimum

  • 1.00 - Min. Display Span

Storage Temperature

  • -25° to 70° C (-13° to 158° F) - Relay Range for Ambient Conditions
  • -25° to 85° C (-13° to 185° F) - Display Range for Ambient Conditions
  • -40° to 85° C (-40° to 185° F) - for Ambient Conditions

Switch Type

  • DPDT Relay, 1 Form C
  • SPDT Relay, 1 Form C

Temperature Effect

  • ± 0.0065 % of Span/°C, Max.

Update Time

  • 100 ms - Display Update Rate

Works with Every Smart HART Device: With a very simple PC program, the HIM programs in minutes to interface with every HART-compatible monitoring and control device:
  • Multivariable Mass Flow Transmitters
  • Dual-Sensor Temperature Transmitters
  • Pressure Transmitters
  • Coriolis, Magnetic, Ultrasonic and Vortex Flow Meters
  • pH Transmitters
  • Radar and Hydrostatic Level Transmitters
  • Valve Positioners and Damper Operators
show more